# RoomAlert 3S

## Overview

Zabbix template for the AVTECH Room Alert 3S environment monitor. This template can be used to monitor the temperature reading from the device's internal thermometer.


To use, create a new host with an SNMP Interface pointing at the IP address of the Room Alert 3S. This interface **must be set to SNMPv1** otherwise it will not be able to read the temperature.


Includes a 'high' alert trigger for temperatures in excess of 25°C and a 'critical' alert trigger for temperatures in excess of 30°C.



## Macros used

There are no macros links in this template.

## Template links

There are no template links in this template.

## Discovery rules

There are no discovery rules in this template.

## Items collected

|Name|Description|Type|Key and additional info|
|----|-----------|----|----|
|Temperature Celcius|<p>Temperature reading from the internal thermometer</p>|`SNMP agent`|temperatureCelcius<p>Update: 1m</p>|


## Triggers

There are no triggers in this template.

Original file line number Diff line number Diff line change
@@ -0,0 +1,59 @@
zabbix_export:
version: '6.0'
date: '2023-04-24T16:02:50Z'
groups:
-
uuid: 7df96b18c230490a9a0a9e2307226338
name: Templates
templates:
-
uuid: a7fed8a83f35402b9f091e7cab302282
template: 'RoomAlert 3S'
name: 'RoomAlert 3S'
groups:
-
name: Templates
items:
-
uuid: 58ba356983814d55b51af5517a565647
name: 'Temperature Celcius'
type: SNMP_AGENT
snmp_oid: .1.3.6.1.4.1.20916.1.13.1.1.1.2.0
key: temperatureCelcius
value_type: FLOAT
units: °C
description: 'Temperature reading from the internal thermometer'
preprocessing:
-
type: MULTIPLIER
parameters:
- '0.01'
-
uuid: 59344a4017ed4dc2b9645e96c391e1e1
name: 'Temperature Fahrenheit'
type: SNMP_AGENT
snmp_oid: .1.3.6.1.4.1.20916.1.13.1.1.1.1.0
key: TemperatureFahrenheit
value_type: FLOAT
units: ºF
description: 'Temperature reading from the internal thermometer'
preprocessing:
-
type: MULTIPLIER
parameters:
- '0.01'
triggers:
-
uuid: e3e1b254b80a42b3b560955481262d3d
expression: 'last(/RoomAlert 3S/TemperatureFahrenheit)>86'
recovery_mode: RECOVERY_EXPRESSION
recovery_expression: 'last(/RoomAlert 3S/TemperatureFahrenheit,#3)<86'
name: 'Critical Temperature Reading - Over 86ºF'
priority: HIGH
-
uuid: 39a433ffa6c6430c8010156e0b392940
expression: 'last(/RoomAlert 3S/TemperatureFahrenheit)>77'
recovery_mode: RECOVERY_EXPRESSION
recovery_expression: 'last(/RoomAlert 3S/TemperatureFahrenheit,#3)<77'
name: 'Temperature Warning - Over 77ºF'
priority: AVERAGE