Correct VAV maximum air flow fraction during reheat for heating dominated use cases #10763
base: develop
Are you sure you want to change the base?
Changes from all commits
90f2846
73fcfff
d29faa1
3473759
1129a59
File filter
Filter by extension
Conversations
Jump to
Diff view
Diff view
There are no files selected for viewing
Original file line number | Diff line number | Diff line change |
---|---|---|
|
@@ -2877,8 +2877,15 @@ void SingleDuctAirTerminal::SizeSys(EnergyPlusData &state) | |
|
||
CheckZoneSizing(state, this->sysType, this->SysName); | ||
|
||
MaxAirVolFlowRateDes = max(state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesCoolVolFlow, | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow); | ||
Real64 heatingMaxFlow; | ||
if (this->DamperHeatingAction == Action::ReverseWithLimits && | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow > | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax) { | ||
heatingMaxFlow = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax; | ||
} else { | ||
heatingMaxFlow = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow; | ||
} | ||
MaxAirVolFlowRateDes = max(state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesCoolVolFlow, heatingMaxFlow); | ||
|
||
if (MaxAirVolFlowRateDes < SmallAirVolFlow) { | ||
MaxAirVolFlowRateDes = 0.0; | ||
|
@@ -2927,7 +2934,13 @@ void SingleDuctAirTerminal::SizeSys(EnergyPlusData &state) | |
} | ||
} else { | ||
CheckZoneSizing(state, this->sysType, this->SysName); | ||
MaxHeatAirVolFlowRateDes = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow; | ||
if (this->DamperHeatingAction == Action::ReverseWithLimits && | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow > | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax) { | ||
MaxHeatAirVolFlowRateDes = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax; | ||
} else { | ||
MaxHeatAirVolFlowRateDes = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow; | ||
} | ||
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. Below at line 3224, ReverseWithLimits uses DesHeatVolFlowMax. That value should also be used here.
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. As discussed above, these 2 areas of code, above (2937) and below (3231), were changed to use DesHeatVolFlowMax as a limit. |
||
if (MaxHeatAirVolFlowRateDes < SmallAirVolFlow) { | ||
MaxHeatAirVolFlowRateDes = 0.0; | ||
} | ||
|
@@ -3215,7 +3228,13 @@ void SingleDuctAirTerminal::SizeSys(EnergyPlusData &state) | |
if (state.dataSize->ZoneSizingRunDone) { | ||
if (state.dataSize->CurTermUnitSizingNum > 0) { | ||
// if zone sizing run done, set the design max reheat air flow to the value from the design calcs | ||
MaxAirVolFlowRateDuringReheatDes = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax; | ||
if (state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow > | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax) { | ||
MaxAirVolFlowRateDuringReheatDes = | ||
state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlowMax; | ||
} else { | ||
MaxAirVolFlowRateDuringReheatDes = state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).DesHeatVolFlow; | ||
} | ||
} | ||
} else { | ||
// if no design calc use 0.002032 [m3/s-m2] times floor area. That's .40 cfm/ft2 | ||
|
@@ -3411,9 +3430,14 @@ void SingleDuctAirTerminal::SizeSys(EnergyPlusData &state) | |
max(state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).NonAirSysDesHeatVolFlow, | ||
this->MaxAirVolFlowRate * this->ZoneTurndownMinAirFrac); | ||
} else { | ||
TermUnitSizing(state.dataSize->CurTermUnitSizingNum).AirVolFlow = | ||
max(state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).NonAirSysDesHeatVolFlow, | ||
this->MaxAirVolFlowRate * this->ZoneMinAirFracDes * this->ZoneTurndownMinAirFrac); | ||
if (this->SysType_Num == SysType::SingleDuctVAVReheat && this->DamperHeatingAction == Action::ReverseWithLimits) { | ||
TermUnitSizing(state.dataSize->CurTermUnitSizingNum).AirVolFlow = | ||
max(this->MaxAirVolFlowRateDuringReheat, this->MaxAirVolFlowRate * this->ZoneTurndownMinAirFrac); | ||
} else { | ||
Comment on lines
-3414
to
+3436
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. So, what if And why is There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. I think I'm landing on falling back on the choices. Normal should size to the minimum flow rate. If that doesn't meet the load then the Reverse or ReverseWithLimits should be used instead. That's what the docs say. And then Reverse and ReverseWithLmits use the corresponding max reheat air flow rate. But that is historically different so I'm stuck with what to do. Regarding the size choice your right. The coil could be over or undersized. I'm not sure the developer should make that sizing choice (i.e., there's plenty of inputs to get it right). One or more of these choices should meet the load. I've also been thinking about heating coil sizing. Zone heating flow rate is SAT - Tzone. TU heating coil sizing is Tout - Tzone. So at the zone heating flow rate you meet the load and that's why NonAirSysDesHeatVolFlow is used. When using actual air flow Reverse should always meet the load, ReverseWithLimits may not. Normal may not meet the load but that's understood with a typical 0.3 minimum stop selection and depends on heating to cooling flow rate ratio. Where's the choice for the user to oversize the heating coil when it operates at a lower flow rate? There is a disconnect between TU heating air flow and heating capacity. Using NonAirSysDesHeatVolFlow to size the coil should always size the coil to meet the load but it seems odd to use a flow rate that differs from the TU and you create a coil outlet temperature that does not match the design criteria. That's when the coil sizing details don't line up with the TU flow rate for maximum flow rate during reheat but you get the right SAT. Some users notice that and question why. There was a lot of testing of these choices and things weren't lining up which created this issue. I'll look at the coil sizing details to see if the issue of TU heating flow rate versus heating coil sizing air flow shows itself. What do you think about a new input to use either the zone or TU heating flow rate? It could default to zone and not change coil capacity (Use Zone Heating Flow Rate to Size Heating Coil, Yes/No). There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. Regarding the reheat coil sizing, there have been many adjustments in the past to make sure that the coil is not way oversized. The airflow is one thing, but I think it uses the zone heating load in the sizing calcs (plus an offset for entering air temp). But that's just my recollection without looking at the code. So, maybe what you have a this point is ok, for ReverseWithLimits, anyway. |
||
TermUnitSizing(state.dataSize->CurTermUnitSizingNum).AirVolFlow = | ||
max(state.dataSize->TermUnitFinalZoneSizing(state.dataSize->CurTermUnitSizingNum).NonAirSysDesHeatVolFlow, | ||
this->MaxAirVolFlowRate * this->ZoneMinAirFracDes * this->ZoneTurndownMinAirFrac); | ||
} | ||
} | ||
} else { | ||
if (this->SysType_Num == SysType::SingleDuctVAVReheatVSFan) { | ||
|
Original file line number | Diff line number | Diff line change |
---|---|---|
|
@@ -1282,7 +1282,7 @@ TEST_F(EnergyPlusFixture, SingleDuct_ZeroFloorAreaTest) | |
// zone floor area of zone 1 = 0, zone 2 > 0. Expect TU MaxAirVolFlowRateDuringReheat = 0 only for zone 1. | ||
// this test isn't relevant anymore since defaulting is done differently | ||
Real64 MaxAirVolFlowRateDuringReheatDes = | ||
min(state->dataSize->FinalZoneSizing(1).DesHeatVolFlowMax, state->dataSingleDuct->sd_airterminal(1).MaxAirVolFlowRate); | ||
min(state->dataSize->FinalZoneSizing(1).DesHeatVolFlow, state->dataSingleDuct->sd_airterminal(1).MaxAirVolFlowRate); | ||
// Real64 MaxAirVolFlowRateDuringReheatDes = min( 0.002032 * state->dataSingleDuct->sd_airterminal( 1 ).ZoneFloorArea, | ||
// state->dataSingleDuct->sd_airterminal( 1 ).MaxAirVolFlowRate ); apply limit based on min stop | ||
MaxAirVolFlowRateDuringReheatDes = | ||
|
@@ -1291,7 +1291,7 @@ TEST_F(EnergyPlusFixture, SingleDuct_ZeroFloorAreaTest) | |
|
||
// This isn't relevant any more since the default is calculated differently | ||
Real64 MaxAirVolFractionDuringReheatDes = | ||
min(1.0, (state->dataSize->FinalZoneSizing(1).DesHeatVolFlowMax / state->dataSingleDuct->sd_airterminal(1).MaxAirVolFlowRate)); | ||
min(1.0, (state->dataSize->FinalZoneSizing(1).DesHeatVolFlow / state->dataSingleDuct->sd_airterminal(1).MaxAirVolFlowRate)); | ||
// Real64 MaxAirVolFractionDuringReheatDes = min( 1.0, ( 0.002032 * state->dataSingleDuct->sd_airterminal( 1 ).ZoneFloorArea / | ||
// state->dataSingleDuct->sd_airterminal( 1 ).MaxAirVolFlowRate ) | ||
// ); apply limit based on min stop | ||
|
@@ -1306,12 +1306,12 @@ TEST_F(EnergyPlusFixture, SingleDuct_ZeroFloorAreaTest) | |
EXPECT_NEAR(MaxAirVolFractionDuringReheatDes, state->dataSingleDuct->sd_airterminal(1).MaxAirVolFractionDuringReheat, 0.0000000000001); | ||
|
||
MaxAirVolFlowRateDuringReheatDes = | ||
min(state->dataSize->FinalZoneSizing(2).DesHeatVolFlowMax, state->dataSingleDuct->sd_airterminal(2).MaxAirVolFlowRate); | ||
min(state->dataSize->FinalZoneSizing(2).DesHeatVolFlow, state->dataSingleDuct->sd_airterminal(2).MaxAirVolFlowRate); | ||
MaxAirVolFlowRateDuringReheatDes = | ||
max(MaxAirVolFlowRateDuringReheatDes, | ||
(state->dataSingleDuct->sd_airterminal(2).MaxAirVolFlowRate * state->dataSingleDuct->sd_airterminal(2).ZoneMinAirFrac)); | ||
MaxAirVolFractionDuringReheatDes = | ||
min(1.0, (state->dataSize->FinalZoneSizing(2).DesHeatVolFlowMax / state->dataSingleDuct->sd_airterminal(2).MaxAirVolFlowRate)); | ||
min(1.0, (state->dataSize->FinalZoneSizing(2).DesHeatVolFlow / state->dataSingleDuct->sd_airterminal(2).MaxAirVolFlowRate)); | ||
MaxAirVolFractionDuringReheatDes = max(MaxAirVolFractionDuringReheatDes, state->dataSingleDuct->sd_airterminal(2).ZoneMinAirFrac); | ||
MaxAirVolFlowRateDuringReheatDes = | ||
min(max(MaxAirVolFlowRateDuringReheatDes, MaxAirVolFractionDuringReheatDes * state->dataSingleDuct->sd_airterminal(2).MaxAirVolFlowRate), | ||
|
@@ -2737,23 +2737,69 @@ TEST_F(EnergyPlusFixture, VAVReheatTerminal_SizeMinFrac) | |
EXPECT_TRUE(compare_err_stream("")); | ||
|
||
int SysNum = 1; | ||
auto &thisSys = state->dataSingleDuct->sd_airterminal(SysNum); | ||
|
||
// First test - design min flow < max flow | ||
state->dataSize->ZoneSizingRunDone = true; | ||
state->dataSize->CurZoneEqNum = 1; | ||
state->dataSize->CurTermUnitSizingNum = 1; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesCoolVolFlowMin = 0.5; | ||
state->dataSingleDuct->sd_airterminal(SysNum).SizeSys(*state); | ||
EXPECT_EQ(0.5, state->dataSingleDuct->sd_airterminal(SysNum).ZoneMinAirFracDes); | ||
thisSys.SizeSys(*state); | ||
EXPECT_EQ(0.5, thisSys.ZoneMinAirFracDes); | ||
|
||
// Second test - design min flow > max flow | ||
state->dataSize->ZoneSizingRunDone = true; | ||
state->dataSize->CurZoneEqNum = 1; | ||
state->dataSize->CurTermUnitSizingNum = 1; | ||
state->dataSingleDuct->sd_airterminal(SysNum).ZoneMinAirFracDes = AutoSize; // need to reset this so it sizes again | ||
thisSys.ZoneMinAirFracDes = AutoSize; // need to reset this so it sizes again | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesCoolVolFlowMin = 1.5; | ||
state->dataSingleDuct->sd_airterminal(SysNum).SizeSys(*state); | ||
EXPECT_EQ(1.0, state->dataSingleDuct->sd_airterminal(SysNum).ZoneMinAirFracDes); | ||
thisSys.SizeSys(*state); | ||
EXPECT_EQ(1.0, thisSys.ZoneMinAirFracDes); | ||
|
||
// test Maximum Flow Fraction During Reheat for heating dominated | ||
thisSys.MaxAirVolFlowRate = DataSizing::AutoSize; | ||
thisSys.ZoneMinAirFracDes = DataSizing::AutoSize; | ||
thisSys.MaxAirVolFlowRateDuringReheat = DataSizing::AutoSize; | ||
thisSys.MaxAirVolFractionDuringReheat = DataSizing::AutoSize; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlow = 1.7; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlowMax = 1.6; | ||
thisSys.SizeSys(*state); | ||
Real64 expectedZoneMinAirFracDes = std::min(1.0, state->dataSize->TermUnitFinalZoneSizing(1).DesCoolVolFlowMin / thisSys.MaxAirVolFlowRate); | ||
// DesHeatVolFlowMax is limiting flow rate | ||
Real64 expectedMaxAirVolFractionDuringReheat = state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlowMax / thisSys.MaxAirVolFlowRate; | ||
EXPECT_EQ(expectedZoneMinAirFracDes, thisSys.ZoneMinAirFracDes); | ||
EXPECT_EQ(1.0, thisSys.MaxAirVolFractionDuringReheat); | ||
EXPECT_EQ(expectedMaxAirVolFractionDuringReheat, thisSys.MaxAirVolFractionDuringReheat); | ||
|
||
// switch magnitude of DesHeatVolFlow and DesHeatVolFlowMax, still heating dominated | ||
thisSys.MaxAirVolFlowRate = DataSizing::AutoSize; | ||
thisSys.ZoneMinAirFracDes = DataSizing::AutoSize; | ||
thisSys.MaxAirVolFlowRateDuringReheat = DataSizing::AutoSize; | ||
thisSys.MaxAirVolFractionDuringReheat = DataSizing::AutoSize; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlow = 1.6; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlowMax = 1.7; | ||
thisSys.SizeSys(*state); | ||
expectedZoneMinAirFracDes = std::min(1.0, state->dataSize->TermUnitFinalZoneSizing(1).DesCoolVolFlowMin / thisSys.MaxAirVolFlowRate); | ||
// DesHeatVolFlowMax is NOT limiting flow rate | ||
expectedMaxAirVolFractionDuringReheat = state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlow / thisSys.MaxAirVolFlowRate; | ||
EXPECT_EQ(expectedZoneMinAirFracDes, thisSys.ZoneMinAirFracDes); | ||
EXPECT_EQ(1.0, thisSys.MaxAirVolFractionDuringReheat); | ||
EXPECT_EQ(expectedMaxAirVolFractionDuringReheat, thisSys.MaxAirVolFractionDuringReheat); | ||
|
||
// test Maximum Flow Fraction During Reheat for cooling dominated | ||
thisSys.MaxAirVolFlowRate = DataSizing::AutoSize; | ||
thisSys.ZoneMinAirFracDes = DataSizing::AutoSize; | ||
thisSys.MaxAirVolFlowRateDuringReheat = DataSizing::AutoSize; | ||
thisSys.MaxAirVolFractionDuringReheat = DataSizing::AutoSize; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlow = 1.4; | ||
state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlowMax = 1.3; | ||
thisSys.SizeSys(*state); | ||
expectedZoneMinAirFracDes = std::min(1.0, state->dataSize->TermUnitFinalZoneSizing(1).DesCoolVolFlowMin / thisSys.MaxAirVolFlowRate); | ||
// DesHeatVolFlowMax is limiting flow rate | ||
expectedMaxAirVolFractionDuringReheat = state->dataSize->TermUnitFinalZoneSizing(1).DesHeatVolFlowMax / thisSys.MaxAirVolFlowRate; | ||
EXPECT_EQ(expectedZoneMinAirFracDes, thisSys.ZoneMinAirFracDes); | ||
EXPECT_EQ(1.0, thisSys.MaxAirVolFractionDuringReheat); | ||
EXPECT_EQ(expectedMaxAirVolFractionDuringReheat, thisSys.MaxAirVolFractionDuringReheat); | ||
There was a problem hiding this comment. Choose a reason for hiding this commentThe reason will be displayed to describe this comment to others. Learn more. Added 3 new tests for maximum air flow fraction during reheat to this unit test. |
||
} | ||
|
||
TEST_F(EnergyPlusFixture, setATMixerSizingProperties_Test) | ||
|
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
If ReverseWithLimits uses a different heating air flow rate from the zone design heating air flow rate then that flow rate should be used as the value for the VAV box heating air flow rate.
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Well, I was expecting DesHeatVolFlowMax to always be less than DesHeatVolFlow. For 5ZoneBoilerOutsideAirReset that's not the case. The diffs show that Zone 5 TU max air flow rate increased, I was only expecting decreases in max air flow rate for heating dominated zones. Zone cooling design air flow is greater than zone heating design air flow, but DesHeatVolFlowMax is larger than both of these.
So is DesHeatVolFlowMax just an upper limit? or is it the expected heating air flow rate?
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
So, since DesHeatVolFlowMax looks like a limit and not a flow rate, maybe I should change this line and line 3224 to?:
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Based on this discussion I changed to treat DesHeatVolFlowMax as an upper limit. This should still correct the issue and result in fewer diffs.