Thanks! works with WVC700-R3 over hc-12 #3
Comments
you are welcome |
Do you know of anyone who has upgraded an inverter from powerline comms to hc-12 comms? ie removed the powerline board from a wvc300 r2 and replaced with an HC-12? I'm running into problems as I see the hc-12 receiving the request( xf2, h1, h2, x65, m1, m2, m3, m4 ) but the tx of the 16F877 remains pulled high at 5V. I've verified the hc-12 works by using it with wvc to send/recv data from an r3 inverter and I verified settings sending AT command to show settings( 9600, FU3 ). |
sorry I know of no one personally |
FYI, I was not having success with an HC-12 connected to a wvc300 which originally had a powerline modem but I wired up a 5V FTDI and talked to it and recieved data. So it looks like the inverters require a 5V variant of the HC-12 or one with level shifters. |
I could not get comms working via the R3 modem either with apps over over RS232 but with an HC-12 on an FTDI dongle your wvc script is talking with the inverters.
Now, to get this integrated into Frey's Node Red system.