Defining JSON user inputs

The simplest way for a user to set up the AFC controller is through a dedicated JSON configuration file, an example can be found here. The json file allows the user to adjust model parameters and preferences without any interaction with the Python code. Below is a list of parameters and their description.

from afc.externalConfig import read_json_config, DEFAULT_JSON_PATH

# Path to json configuration
json_config_path = DEFAULT_JSON_PATH

# Create the inputs vector
parameter = read_json_config(json_config_path)
inputs = make_inputs(parameter, wf)
  • building_age: [str] Indicator of building vintage. Used to update parameter['zone']['param']. Default value is 'new-constr'. Possible values are 'new-constr', 'post-1980' and 'pre-1980'.
  • debug: [bool] Flag to enable console printing of the solver. Used to update parameter['wrapper']['printing']. Default value is 'False'.
  • interface_status: [str] Status from the user interface. Default value is 'Updated Configuration'.
  • location_city: [str] City location of the building. Default value is 'Berkeley'.
  • location_latitude: [float] Latitude of the building, in degree. Used to update parameter['radiance']['location']['latitude']. Default value is 37.85.
  • location_longitude: [float] Longitude of the building, in degree. Used to update parameter['radiance']['location']['longitude']. Default value is -122.24.
  • location_orientation: [float] Orientation of the building, in degree. Note that 0 corresponds to South, 90 is West, -90 is East, and 180 is North. Used to update parameter['radiance']['location']['orientation']. Default value is 0.
  • location_state: [str] State location of the building. Default value is 'CA'.
  • occupant_1_direction [float] Orientation of the occupant inside the building, in degree relative to the building orientation. For a location_orientation of 90 deg (West), a occupant_1_direction of -90 corresponds to a view towards South. Used to update parameter['radiance']['location']['view_orient']. Default value is 0.
  • occupant_brightness [float] Occupant preference for minimum work plane illuminance, in percent. 80% corresponds to 250 lux, 100% to 350 lux, and 120% to 450 lux. Used to map parameter['occupant']['wpi_min']. Default value is 100% (350 lux).
  • occupant_glare [float] Occupant preference for maximum acceptable glare, in percent. 80% corresponds to dpg of 0.3, 100% to 0.4, and 120% to 0.5. Used to map parameter['occupant']['glare_max']. Default value is 100% (0.4).
  • occupant_number [int] Number of occupants in the room. Used as multiple to update unitary metrics such as the electric equipment load (parameter['occupant']['equipment']), thermal plug load (parameter['occupant']['plug_load']) and thermal occupant load (parameter['occupant']['occupant_load']). Default value is 1.
  • room_depth [float] Depth of the building, in feet. Used to update parameter['radiance']['dimensions']['depth']. Default value is 15.
  • room_height [float] Height of the building, in feet. Used to update parameter['radiance']['dimensions']['height']. Default value is 11.
  • room_width [float] Width of the building, in feet. Used to update parameter['radiance']['dimensions']['width']. Default value is 10.
  • system_cooling [str] Type of energy used by the cooling system. Default value is 'el' (for electric). No other technologies are implemented at this time.
  • system_cooling_eff [float] The coefficient of performance of the cooling system. Used to update parameter['zone']['cooling_efficiency']. Default value is 3.5.
  • system_heating [str] Type of energy used by the heating system. Default value is 'el' (for electric). No other technologies are implemented at this time.
  • system_heating_eff [float] Electric efficiency of the heating system. If the heating system type is electric, then it is used to update parameter['zone']['heating_efficiency']. Otherwise, the latter parameter is set to 1. Default value is 0.95.
  • system_id [str] Unique instance identifier. Used to update parameter['wrapper']['instance_id']. Default value is 'Test-AAA'.
  • system_light [str] Type of the lighting system. Used to map parameter['zone']['lighting_efficiency']. Possible values are fluorescent ('FLU') which sets efficiency to 0.5 W/lux and 'LED' which sets it to 0.25 W/lux. Default value is 'LED'.
  • system_type [str] Type of the facade. Used to update parameter['facade']['type']. Currently only supports the default (three-zone electrochromic window). Default value is 'ec-71t'.
  • tariff_name [str] Name of the used tariff rate. Used to update parameter['wrapper']['tariff_name']. A full list of available tariffs can be found in the DOPER documentation here. Default value is 'e19-2020'.
  • window_count [int] Number of windows on the building facade. Used to multiply the window width. Used to update the coordinates in parameter['radiance']['dimensions']['windows1'], parameter['radiance']['dimensions']['windows2'], and parameter['radiance']['dimensions']['windows3']. Default value is 2.
  • window_height [float] Height of a window, in feet. Used to update the coordinates in parameter['radiance']['dimensions']['windows1'], parameter['radiance']['dimensions']['windows2'], and parameter['radiance']['dimensions']['windows3']. Default value is 8.5.
  • window_sill [float] Sill of a window, in feet. Used to update the coordinates in parameter['radiance']['dimensions']['windows1'], parameter['radiance']['dimensions']['windows2'], and parameter['radiance']['dimensions']['windows3']. Default value is 0.5.
  • window_width [float] Width of a window, in feet. Used to update the coordinates in parameter['radiance']['dimensions']['windows1'], parameter['radiance']['dimensions']['windows2'], and parameter['radiance']['dimensions']['windows3']. Default value is 4.5.